eLaws of Florida

  SECTION 403.0882. Discharge of demineralization concentrate.  


Latest version.
  • 1(1) 2The Legislature finds and declares that it is in the public interest to conserve and protect water resources, provide adequate water supplies and provide for natural systems, and promote brackish water demineralization as an alternative to withdrawals of freshwater groundwater and surface water by removing institutional barriers to demineralization and, through research, including demonstration projects, to advance water and water byproduct treatment technology, sound waste byproduct disposal methods, and regional solutions to water resources issues. In order to promote the state objective of alternative water supply development, including the use of demineralization technologies, and to encourage the conservation and protection of the state’s natural resources, the concentrate resulting from demineralization must be classified as potable water byproduct regardless of flow quantity and must be appropriately treated and discharged or reused.
    132(2) 133For the purposes of this section, the term:
    141(a) 142“Demineralization concentrate” means the concentrated byproduct water, brine, or reject water produced by ion exchange or membrane separation technologies such as reverse osmosis, membrane softening, ultrafiltration, membrane filtration, electrodialysis, and electrodialysis reversal used for desalination, softening, or reducing total dissolved solids during water treatment for public water supply purposes.
    191(b) 192“Small water utility business” means any facility that distributes potable water to two or more customers with a concentrate discharge of less than 50,000 gallons per day.
    220(3) 221The department shall initiate rulemaking no later than October 1, 2001, to address facilities that discharge demineralization concentrate. The department shall convene a technical advisory committee to assist in the development of the rules, which committee shall include one representative each from the demineralization industry, local government, water and wastewater utilities, the engineering profession, business, and environmental organizations. The technical advisory committee shall also include one member representing the five water management districts and one representative from the Fish and Wildlife Research Institute. In convening the technical advisory committee, consideration must be given to geographical balance. The rules must address, at a minimum:
    324(a) 325Permit application forms for concentrate disposal;
    331(b) 332Specific options and requirements for demineralization concentrate disposal, including a standardized list of effluent and monitoring parameters, which may be adjusted or expanded by the department as necessary to protect water quality;
    364(c) 365Specific requirements and accepted methods for evaluating mixing of effluent in receiving waters; and
    379(d) 380Specific toxicity provisions.
    383(4)(a) 384For facilities that discharge demineralization concentrate, the failure of whole effluent toxicity tests predominantly due to the presence of constituents naturally occurring in the source water, limited to calcium, potassium, sodium, magnesium, chloride, bromide, and other constituents designated by the department, may not be the basis for denial of a permit, denial of a permit renewal, revocation of a permit, or other enforcement action by the department as long as the volume of water necessary to achieve water quality standards is available within a distance not in excess of two times the natural water depth at the point of discharge under all flow conditions.
    488(b) 489If failure of whole effluent toxicity tests is due predominately to the presence of the naturally occurring constituents identified in paragraph (a), the department shall issue a permit for the demineralization concentrate discharge if:
    5231. 524The volume of water necessary to achieve water quality standards is available within a distance not in excess of two times the natural water depth at the point of discharge under all flow conditions; and
    5592. 560All other permitting requirements are met.

    566A variance for toxicity under the circumstance described in this paragraph is not required.

    580(c) 581Facilities that fail to meet the requirements of this subsection may be permitted in accordance with department rule, including all applicable moderating provisions such as variances, exemptions, and mixing zones.
    611(5) 612Blending of demineralization concentrate with reclaimed water shall be allowed in accordance with the department’s reuse rules.
    629(6) 630This subsection applies only to small water utility businesses.
    639(a) 640The discharge of demineralization concentrate from small water utility businesses is presumed to be allowable and permittable in all waters in the state if:
    6641. 665The discharge meets the effluent limitations in s. 673403.086(4), 674except that high level disinfection is not required unless the presence of fecal coliforms in the source water will result in the discharge not meeting applicable water quality standards;
    7032. 704The discharge of demineralization concentrate achieves a minimum of 4-to-1 dilution within a distance not in excess of two times the natural water depth at the point of discharge under all flow conditions; and
    7383. 739The point of discharge is located at a reasonably accessible point that minimizes water quality impacts to the greatest extent possible.
    760(b) 761The presumption in paragraph (a) may be overcome only by a demonstration that one or more of the following conditions is present:
    7831. 784The discharge will be made directly into an Outstanding Florida Water, except as provided in chapter 90-262, Laws of Florida;
    8042. 805The discharge will be made directly to Class I or Class II waters;
    8183. 819The discharge will be made to a water body having a total maximum daily load established by the department and the discharge will cause or contribute to a violation of the established load;
    8524. 853The discharge fails to meet the requirements of the antidegradation policy contained in the department rules;
    8695. 870The discharge will be made to a sole-source aquifer;
    8796. 880The discharge fails to meet applicable surface water and groundwater quality standards; or
    8937. 894The results of any toxicity test performed by the applicant under paragraph (d) or by the department indicate that the discharge does not meet toxicity requirements at the boundary of the mixing zone under subparagraph (a)2.
    930(c) 931If one or more of the conditions in paragraph (b) has been demonstrated, the department may:
    9471. 948Require more stringent effluent limitations;
    9532. 954Require relocation of the discharge point or a change in the method of discharge;
    9683. 969Limit the duration or volume of the discharge; or
    9784. 979Prohibit the discharge if there is no alternative that meets the conditions of subparagraphs 1.-3.
    994(d) 995For facilities owned by small water utility businesses, the department may not:
    10071. 1008Require those businesses to perform toxicity testing at other than the time of permit application, permit renewal, or any requested permit modification, unless the initial toxicity test or any subsequent toxicity test performed by the department does not meet toxicity requirements.
    10492. 1050Require those businesses to obtain a water-quality-based effluent limitation determination.
    1060(7) 1061The department may adopt additional rules for the regulation of demineralization and to administer this section and s. 1079403.061(11)(b)1080.
History.-s. 43, ch. 97-160; s. 1, ch. 2001-188; s. 12, ch. 2004-264.